Why This Matters on a Plant Floor
A distribution panel breaker that trips during a fault on a single branch can bring down an entire factory section. A breaker that does not trip leaves equipment unprotected. Specifying the wrong frame size, breaking capacity, or trip settings wastes budget on undersized panels that need rebuilding, or oversized ones that leave no room for growth.
An incorrect breaking capacity invites a failed compliance inspection. The panel assembly must be rated for the installed breaker. If the panel assembly short-circuit rating is lower than the Psc or the installed breaker rating, the assembly may not comply with IEC 61439 and should be reviewed before use. Nuisance trips from wrong trip curves cost production hours. A plant engineer in Vapi or Navsari cannot afford these errors: an unplanned shutdown is far better avoided by getting the specification right from the start.
Frame Size Sets the Maximum Rating and Capacity
Frame size is the physical envelope of the breaker: it determines how much current the breaker can carry continuously and how much fault current it can interrupt. Smaller frames cannot handle larger loads.
Legrand DPX3 MCCBs are available in frame sizes that deliver current ratings from 16 A to 1600 A. Each frame size has a defined maximum short-circuit breaking capacity (Icu). Each frame has its own Icu, from 16 kA up to 100 kA across the range, so check the datasheet for the exact version and frame.
Do not confuse frame size with setting. A 250 A frame MCCB with an adjustable trip unit can be set to trip at a lower current, such as 160 A, depending on the load. The frame itself limits the maximum, not the setting.
Breaking Capacity Must Match the Fault Level
Short-circuit breaking capacity comes in two ratings.
Icu (ultimate short-circuit breaking capacity) is the maximum fault current the breaker can interrupt once. After that event, the breaker must be replaced.
Ics (service breaking capacity) is the level at which the breaker can trip and continue to operate without replacement. Ics is usually 70% to 100% of Icu.
The prospective short-circuit current (Psc) at the installation point must be calculated using the utility fault level, transformer impedance, and cable sizes. The breaker Icu must equal or exceed Psc. If Psc is 45 kA and the breaker Icu is 36 kA, the breaker is not rated to interrupt that fault safely and must not be used.
| Legrand DPX3 Frame | Current Rating Range | Breaking Capacity (Icu) | Typical Application |
|---|---|---|---|
| Lower frames | From 16 A | From 16 kA | Branch circuits, submain feeders |
| Mid frames, including 250 A | Check datasheet | Check datasheet, up to 100 kA | Submain feeders, transformers, generators |
| Largest frames | Up to 1600 A | Up to 100 kA | High-current incomers |
To verify breaking capacity, take the calculated Psc and compare it with the Icu published in the Legrand DPX3 datasheet. Check that the Icu equals or exceeds your Psc. If not, specify a higher-rated version and confirm with a licensed electrical contractor.
Trip Curves: B, C and D for Different Loads
The trip curve defines how fast the breaker opens when current exceeds the setting. Curves B, C and D are defined for MCBs such as the Legrand DX3; MCCBs use adjustable thermal-magnetic or electronic settings with comparable thresholds.
Curve B trips at roughly 3–5 times the current setting (In). Use B for purely resistive loads such as heating, lighting, and panel instruments. Curve B is rarely used in factory mains because loads have inrush.
Curve C trips at roughly 5–10 times In. Use C for mixed loads, office equipment, and small motors up to 2–3 kW. Most branch circuits in a modern factory use curve C.
Curve D trips at roughly 10–20 times In. Use D for transformer inrush, large motors above 5 kW, and compressors. Curve D allows high inrush during start without tripping, then protects if the current stays high (indicating a stall or overload).
Wrong curve selection causes two problems. If you specify curve B for a motor feeder, the breaker trips during normal start. If you specify curve C for a transformer incomer, the breaker may trip on transformer inrush when energised.
For a mixed factory with offices, motors, and transformers, use curve C for most branch circuits and curve D for the main incomer and transformer protection circuits. Ask the load engineer which branch has motors or transformers, then check the datasheet for the inrush value. Check the DPX3 datasheet for the available magnetic trip settings.
Selectivity: Preventing Unwanted Cascade Trips
Selectivity means that when a fault occurs in a branch circuit, only that branch breaker trips, not the main incomer. If the incomer trips first, all downstream circuits lose power.
Selectivity is verified by comparing time-current coordination curves. The downstream breaker must trip faster (at a lower time) than the upstream breaker for the same fault current. The gap between the two curves at the expected fault current determines selectivity margin. The required margin depends on the devices, so use the manufacturer's tables.
Legrand publishes discrimination tables for DPX3 MCCBs paired with downstream MCBs, MCCBs, and fusegear. To verify selectivity, enter the upstream breaker model and setting, the downstream breaker model and setting, and the expected fault current at that point. The table confirms or rejects selectivity. Do not use curves from different manufacturers: an ABB MCCB curve and a Legrand MCCB curve are not directly comparable and may show false selectivity.
Electronic trip units in Legrand DPX3 MCCBs offer long-time, short-time, and instantaneous functions with adjustable thresholds. These allow finer tuning than thermal-magnetic relays. For a factory with a complex load structure, electronic trip offers better selectivity and fewer nuisance trips. Confirm in the RFQ whether electronic trip is required and specify the exact settings (long-time delay, short-time threshold, instantaneous threshold) so the factory does not use defaults that do not match your scheme.
Worked Example: A Factory Submain Feeder
A textile mill in Navsari has a 315 kVA transformer with 6% impedance, feeding a panel where the calculated fault level is about 35 kA. The transformer feeds a submain distribution panel 30 m away using 4 × 95 mm² cables. The submain supplies three branch feeders: a 45 kW motor, lighting and 20 kW of heating.
Step 1: Calculate prospective short-circuit current at the submain panel. A 315 kVA, 6% transformer at 415 V gives roughly 7.3 kA at its terminals, so the submain fault level is below that. Use the calculated Psc for your own site.
Step 2: Select the submain incomer. A DPX3 MCCB with a 160 A rating and adequate Icu is suitable. Set the magnetic threshold high enough to ride through transformer inrush.
Step 3: Select branch breakers. The 45 kW motor draws approximately 80 A at full load, with a starting current of several times that. A 100 A DPX3 MCCB with a suitable magnetic setting is suitable. The 20 kW heating load draws approximately 29 A at 415 V three-phase, so a 32 A to 40 A breaker is adequate.
Step 4: Verify selectivity between the submain (160 A) and the motor branch (100 A) using the Legrand discrimination table for this pair. Selectivity holds only up to the limit stated in the table, so compare that limit with the fault current at the motor branch.
Step 5: Verify panel breaking capacity. Confirm the short-circuit rating of the assembly from the manufacturer's documentation and check it matches or exceeds the fault level at the panel. If it does not, a higher-rated assembly must be specified.
Standards Compliance
Legrand MCCBs and ACBs are designed to IEC 60947-2, the international standard for low-voltage switchgear and controlgear (circuit-breakers). IEC 61439 (low-voltage switchgear and controlgear assemblies) governs the panel assembly rating. Refer to the current editions of IEC 60947-2 and IEC 61439, and confirm the panel assembly rating and breaker coordination with your licensed electrical contractor before final order.
What We Stock Against This Requirement
Vimal Electric Corporation supplies Legrand DPX3 MCCBs and Ekinox distribution boards to factories across south Gujarat. DPX3 MCCBs are available from 16 A to 1600 A; ask the counter about availability and ratings.
To specify correctly, send your load list and single-line diagram to our industrial team. Include the utility fault level, transformer impedance if applicable, cable sizes, and the connected loads on each branch. Our industrial team will help match your requirement to the Legrand range; frame sizing, selectivity and panel assembly rating should be verified by your licensed electrical contractor or panel builder.